8.5 Heat Accumulator

Ⅰ Dominant Items

8.5.1 The hydrostatic test of heat accumulator shall comply with the requirement of the design technical document.

Quantity to be checked:100%.

Inspection method:Observe,and check the pressure test record.

8.5.2 The movable base of heat accumulator shall be reserved with the movement amount for thermal expansion and without any obstruction according to the requirement of the design technical document.

Quantity to be checked:100%.

Inspection method:Observe,and measure by a ruler.

Ⅱ General Items

8.5.3 The allowable deviation for installation of heat accumulator shall comply with the requirements in Table 8.5.3.

Quantity to be checked:100%.

Inspection method:See Table 8.5.3.

Table 8.5.3 Allowable deviation for installation of heat accumulator

img